SB6100 Series - Ground-Fault Circuit Interrupter (GFCI) and Equipment Ground-Fault Protective Device (EGFPD)

DataSheet:Download SB6100 Datasheet

Special Purpose Ground-Fault Circuit Interrupter (GFCI),Class C and Class D

The Industrial Shock-Block is the first permanently connected special-purpose GFCI that meets UL Standard 943C Class C and Class D—designed for people protection in industrial facilities. According to UL 943C, special-purpose GFCI’s can be used in the following applications:
  • On grounded-neutral systems where voltage to ground is above 150 Vac and equipment grounding or double insulation is required by the NEC®, ANSI and NFPA 70.
  • On grounded-neutral systems where voltage to ground is 150 Vac or less and equipment grounding or double insulation is provided, but the use of a Class A ground-fault circuit interrupter is not practical.
  • Any CEC application in which a Class A GFCI is not required.

Equipment Ground-Fault Protective Device (EGFPD)

The Industrial Shock-Block is available with adjustable protection settings as an EGFPD. The EGFPD models (hardware revision 1) can be set to trip at 6mA, and 10 to 100mA in increments of 10mA. This helps reduce nuisance tripping in systems with leakage current higher than the standard 6 mA required by UL 943 Class A GFCI (GFCI devices are not allowed to have an adjustable trip level).

All ordering options include CSA certification.

Ordering Information
Catalog #Conformally Coated PWBDimensionsFrequency (Hz)Full Load Current (A)GF Trip Level (A)NEMA RatingRelayContactsRelayContactOperatingModeSystem TypeSupplyVoltage(VAC)
SB6100-000-0Standard455.0 x 340.7 mmx 174.9 mm6010020 mAOne Form A (N.O.)Fail-safe208
SB6100-001-0Standard453.8x 406.2 mmx 223.3 mm6010020 mANEMA 4XOne Form A (N.O.)Fail-safeGrounded208
SB6100-010-0Standard455.0 x 340.7 mmx 174.9 mm601006, 10-100 mA in increments of 10 mAOne Form A (N.O.)Fail-safeGrounded208
SB6100-011-0Standard453.8x 406.2 mmx 223.3 mm601006, 10-100 mA in increments of 10 mANEMA 4XOne Form A (N.O.)Fail-safeGrounded208
SB6100-100-0Standard455.0 x 340.7 mmx 174.9 mm6010020 mAOne Form A (N.O.)Fail-safeGrounded240
SB6100-101-0Standard453.8x 406.2 mmx 223.3 mm6010020 mANEMA 4XOne Form A (N.O.)Fail-safeGrounded240
SB6100-110-0Standard455.0 x 340.7 mmx 174.9 mm601006, 10-100 mA in increments of 10 mAOne Form A (N.O.)Fail-safeGrounded240
SB6100-111-0Standard453.8x 406.2 mmx 223.3 mm601006, 10-100 mA in increments of 10 mANEMA 4XOne Form A (N.O.)Fail-safeGrounded240
SB6100-200-0Standard455.0 x 340.7 mmx 174.9 mm6010020 mAOne Form A (N.O.)Fail-safeGrounded480
SB6100-201-0Standard453.8x 406.2 mmx 223.3 mm6010020 mANEMA 4XOne Form A (N.O.)Fail-safeGrounded480
SB6100-210-0Standard455.0 x 340.7 mmx 174.9 mm601006, 10-100 mA in increments of 10 mAOne Form A (N.O.)Fail-safeGrounded480
SB6100-211-0Standard453.8x 406.2 mmx 223.3 mm601006, 10-100 mA in increments of 10 mANEMA 4XOne Form A (N.O.)Fail-safeGrounded480
SB6100-300-0Standard455.0 x 340.7 mmx 174.9 mm6010020 mAOne Form A (N.O.)Fail-safeGrounded600
SB6100-301-0Standard453.8x 406.2 mmx 223.3 mm6010020 mANEMA 4XOne Form A (N.O.)Fail-safeGrounded600
SB6100-310-0Standard455.0 x 340.7 mmx 174.9 mm601006, 10-100 mA in increments of 10 mAOne Form A (N.O.)Fail-safeGrounded600
SB6100-311-0Standard453.8x 406.2 mmx 223.3 mm601006, 10-100 mA in increments of 10 mANEMA 4XOne Form A (N.O.)Fail-safeGrounded600
Resources
Download Industrial Shock-Block Datasheet ac6000-industrial-shock-block-cart
SB6100 Manual sb6000
Industrial Shock-Block Brochure sb6000
SB6000 Industrial Shock-Block Enclosed CAD sb6000
SB6000 Industrial Shock-Block Open Chassis CAD sb6000
Industrial Shock-Block SB6100 FAQ sb6000
Industrial Shock-Block GFCI WhitePaper sb6000
SB6000